If you have defined trend graphs and a log book with many variables or with many samples to store, the default buffer size (64K) of the data sever may be too small.
When you download your logBook you will have the following error:
Load Error: Load [20040008]
Not enough memory (buffer)
To change the buffer size:
- If your data server is running under Windows change the following in HabDts.ini:
[HMM]
BlockSize=128
- If your data server is running on another system, start the data server with the following command line:
HabDts -HMM\BlockSize=128